Huawei Digital Power's C&I GFM ESS Passes Extreme Ignition Test

Huawei

SHENZHEN, China, Dec. 16, 2025 /PRNewswire/ -- Huawei Digital Power's Commercial and Industrial Hybrid Cooling Grid Forming Energy Storage System (C&I GFM ESS) has successfully passed a stringent extreme ignition test witnessed by TÜV Rheinland. Conducted at a national key fire safety lab, the test is the industry's first fire assessment of an ESS in compliance with the latest UL 9540A:2025 standard.

 

Huawei Digital Power's C&I GFM ESS Passes Extreme Ignition Test

 

Extreme Challenge: Rigorous Test Environment

 

The test was designed to create the industry's most demanding verification environment, evaluating the safety performance of ESSs under extreme ignition scenarios. A pack-level overcharge method was used to trigger simultaneous thermal runaway in 60 battery cells. Compared with tests involving only single or a few cells, the severity of this assessment increases exponentially.

 

Further rigor was ensured through the following conditions:

 

 1. The open-door ignition test method specified in UL 9540A:2025 is employed to maximize oxygen availability.
 2. All packs are fully charged to 100% SOC.
 3. All proactive and passive fire suppression systems are disabled during testing, requiring the ESSs to rely solely on their intrinsic design to withstand combustion at full energy capacity.

 

Proven Strength: Five-Level Protection System

 

Under these extreme conditions, Huawei's C&I GFM ESS demonstrated outstanding safety performance, supported by its innovative five-level protection design.

 

 1. Inter-cell thermal isolation: It effectively slows down the thermal runaway propagation between cells, providing the first defense for system safety.

 2. All-metal pack enclosure: The enclosure can withstand temperatures higher than 1500°C, maintaining structural integrity even under intense fire to minimize damage.
 3. Positive-pressure oxygen blocking and directional smoke exhaust: This innovative design redirects combustibles, significantly reducing fire impact.
 4. Fireproof labyrinth design: All ESS sealing surfaces feature a labyrinth structure to effectively prevent flame spread.
 5. Enhanced container fire resistance: The container is armored to provide comprehensive fire protection.

 

Data Evidence: Key Indicators Demonstrating Excellent Performance

 

Test data robustly validates the safety and reliability of Huawei's C&I GFM ESS. When the fire temperature reached961°C, the highest cell temperature of an adjacent ESS was only 45.3°C, well below the threshold for opening the cell explosion-proof valve. The system fully complied with UL 9540A:2025 requirements, with no fire propagation between units.

 

The recorded peak heat release rate (HRR) was 3 MW. Total combustion lasted less than three hours before self-extinguishing. Under open-door burning conditions, the system rapidly managed heat release, demonstrating superior thermal management capability.

 

PR Newswire Asia Ltd.

 

 

PR Newswire
1954年に設立された世界初の米国広報通信社です。配信ネットワークで全世界をカバーしています。Cision Ltd.の子会社として、Cisionクラウドベースコミュニケーション製品、世界最大のマルチチャネル、多文化コンテンツ普及ネットワークと包括的なワークフローツールおよびプラットフォームを組み合わせることで、様々な組織のストーリーを支えています。www.prnasia.com

本プレスリリースは発表元が入力した原稿をそのまま掲載しております。また、プレスリリースへのお問い合わせは発表元に直接お願いいたします。

プレスリリース添付画像

このプレスリリースには、報道機関向けの情報があります。

プレス会員登録を行うと、広報担当者の連絡先や、イベント・記者会見の情報など、報道機関だけに公開する情報が閲覧できるようになります。

プレスリリース受信に関するご案内

SNSでも最新のプレスリリース情報をいち早く配信中